深圳市英达制冷机电有限公司
店龄6年 · 企业认证 · 广东省深圳市
手机扫码查看 移动端的落地页
深圳市英达制冷机电有限公司
主营产品: 膨胀阀, 电磁阀, 真空泵, 压力表, 单向阀, 截止阀, 压力控制器, 流量计, 水阀, 真空表, 四通阀, 球阀, 蒸发压力调节器, 冷凝压力调节器, 温度控制器, 四通换向阀, 压力开关, 空调加氟管, 能量调节器, 手阀, 电子膨胀阀, 压力式制水阀, 温度表, 真空计, 电磁四通阀, 水流开关, 检漏仪, 冷媒回收机, 加氟软管, 油压表, 棘轮扳手, 扩口器, 快速接头, 电子秤, 冷凝器风扇调速器, 水泵, 压力传感器, 导阀, 安全阀, 视液镜, 油分离器, 温度探头, 板式交换器, 热交换器, 分液头, 曲轴箱压力调节器, 蒸发器控制器
韩国3WIN不锈钢避震管HJ-2压缩机吸气排气用减震管1/2
价格
订货量(个)
¥10000.00
≥1
店铺主推品 热销潜力款
잵잰잲잭잰잴잳잴잯잱잮
在线客服
1. Exercise proper techniques when installing these
vibration absorbers.
A. Apply a heat block paste such as thermal block or
wet rag to the brazed joint between the copper
socket and the stainless steel ferrule on the
vibration absorber prior to heating.
B. Heat the copper tube going into the copper
socket first, then apply heat to the copper socket
and apply solder to finish the connection.
C. Always direct flame away from the vibration
absorber.
2. It is recommended that a soft silver bearing solder be
used to make the joint as excessive heat can damage
the vibration absorber.
3. Vibration absorbers are designed to absorb shock and
vibration perpendicular to the direction fo installation.
They are not designed to absorb shock in the form of
sudden tension or compression loading along its long
axis. The Vibration absorber series should only be
installed in a straight line, never offset to compensate
for misaligned piping or other improper installation
techniques.
If the vibration absorber is to be used in a suction line
that will go below the freezing point, the entire vibration
absorber should be wrapped with a waterproof barrier.
This is to prevent condensation from forming and
freezing under the braid which can collapse the
convolutions, possibly resulting in leaks.
5.
For best res ults, the vibration absorber should be
installed as close to the compressor as possible along
the axis of the compressor's crankshaft, since this is
the most common source of vibration, and anchored to
a solid structure at the end farthest away from the
compressor(see figure below). If vibrations occur in
both the vertical and horizontal directions, place two
vibration absorbers.